ދިވެހިރާއްޖެ
އަންދާސީހިސާބު ބޭނުންވެއްޖެ
މި އޮތޯރިޓީއަށް ޑާޓާ ސެންޓަރ ކޫލިން ސިސްޓަމެއް ތިރީގައިވާ ސްޕެސިފިކޭޝަނާ އެއްގޮތްވާ ގޮތުގެމަތީން ސަޕްލައިކޮށް އިންސްޓޯލް ކޮށްދޭނެ ފަރާތެއް ހޯދަން ބޭނުންވެއެވެ.
Table 1: Cooling Specification
|
|
Type |
Detail |
|
Type |
In-Row Cooling System |
|
|
Application |
Cooling for Critical Electrical Applications |
Currently 5 Racks. System should be able to scale for extra 1 OR 2 Racks |
|
Humidity Regulation |
Yes |
To help avoid electrostatic charge |
|
Temperature |
Average ~ 22 Degrees |
Cold Aisle should maintain the temperature. |
|
Cycle of Operation |
24 x 7 x 365 operation |
|
|
Environment |
Monitoring Capability |
Air sensor, temperature, humidity |
|
Total IT load |
~ 12,600 Watts |
Estimated combine capacity of the IT equipment’s in the racks |
|
Redundancy |
N+1 configuration |
|
|
Total Cooling |
~ 16,000 Watts |
Estimated amount calculated with +/- 2kW (Bidder should be able to cater this amount) |
|
Management |
Web Management |
SNMP and HTTP web-management communications capabilities for monitoring |
|
Other |
- Temperature sensors - Water Leak Detector |
Rack base temperature sensors to monitor inlet of airflow Water Leak Detector for the solution proposed |
Table 2: Data Centre Space
|
Type |
Detail |
|
|
Size |
32.93 sq. m |
Refer to Diagram 01 |
|
Power System Rating |
16,000 Watts |
Centralized UPS power capacity |
|
Raised Floor |
No |
|
|
Housing of outdoor Units |
Roof top |
Piping duct is present next to Data Centre |
ވީމާ، މިކަމަށް ޝައުޤުވެރިވާ ފަރާތްތަކުން ތިރީގައި މިދަންނަވާ ދުވަސްތަކުގައި މިއޮތޯރިޓީއަށް ވަޑައިގެން މަޢުލޫމާތު ސާފުކުރެއްވުމަށްފަހު އަންދާސީހިސާބު ހުށަހެޅުއްވުން އެދެމެވެ.
|
ތަފުސީލު |
ތާރީޚު |
ދުވަސް |
ގަޑި |
|
މަޢުލޫމާތު ސާފުކުރުން |
04 ޖޫން 2015 |
ބުރާސްފަތި |
10:00 |
|
އަންދާސީހިސާބު ހުށަހެޅުން |
15 ޖޫން 2015 |
ހޯމަ |
11:00 |
މިކަމަށް އަންދާސީހިސާބު ހުށަހެޅޭނީ މަޢުލޫމާތު ސާފުކުރުމަށް އަންގާފައިވާ ދުވަހު ހާޒިރުވެ މަޢުލޫމާތު ސާފުކުރައްވާ ފަރާތްތަކަށެވެ.
10 ޝަޢުބާން 1436