މިކުންފުންޏަށް ތިރީގައިވާ މަޢުލޫމާތާ އެއްގޮތަށް ދަންނަވާފައިވާ ތަކެތި ގަތުމަށް ކުރެވުނު ނަންބަރު FNK-K(T)/FNK/IUL/2014/125ފ(02 އޮކްޓޫބަރު 2014) އިޢުލާނަށް އެކަށީގެންވާ ތަރުޙީބެއް ލިބިފައިނުވާތީ، މިފުރުޞަތު މިކަމަށް ޝައުޤުވެރިވެލައްވާ ފަރާތްތަކަށް އަލުން ހުޅުވާލަމެވެ. ވީމާ, މިކުންފުންޏަށް ތިރީގައިވާ މަޢުލޫމާތާ އެއްގޮތަށް މިދަންނަވާ ތަކެތި ގަންނަން ބޭނުންވެއެވެ.
Specification of Auto Synchronizing and Load Sharing Auto/Manual Start/Stop Panel Board
Specification of Panel Board Cubicles shall be made from high quality steel frame and plates and shall be assembled keep in mind to easy maintenance. Paints applied on the cubicles shall be durable and suitable for harsh environment. Component such as isolators, bus bars, relays, switches and instruments shall be from reputable manufacturer. Synchronizing panels and distribution panels shall fully comply with relevant international standards. The panel shall be manufactured using power coated mild steel sheets of 1.6 mm thickness. The thickness of the front door panel shall be 2.4 mm. a strong base frame of 100mm tall shall be provided with the panel board. The panel board shall be a free standing, bottom cable entry type panel. |
Unit |
Qty |
Item Details |
S/N |
Nos |
01 |
Air Circuit Breaker Control panel (7 cubicles) – (Control Panel): 1) Bus bar TP and N (same size neutral) hard drain high copper conductivity air insulated tinned bus bar shall be provided at the back of the enclosure, stably brace for 30kA – 80kA 1- second fault rating. The current rating of bus bar shall be 6000A. 2) Air Circuit Breaker 5 x Three pole Merlin Gerin or equivalent ACB, rated at 2000 Amp @ 600/1000V with 220 Volt under Voltage Trip Coil and 5 Ampere rated auxiliary switches shall be used as a main circuit breaker for each generator incoming. 2 x Three pole Merlin Gerin or equivalent ABC, rated at 2000 Amp @ 600/1000V with 220 Volt under Voltage Trip Coil and 5 Ampere rated auxiliary switches shall be used as a main circuit breaker for each transformer feeding panel. 3) Indicators Led indicator shall be fixed on each phase of generator incoming, bus bar and transformer feeding panels. And also LED indicator lights shall be fixed to indicate the ACB position. 4) Current Transformers 4 numbers of 2000/5A, class1, 15VA current transformers shall be fixed on each generator incoming side and 4 numbers of 4000/5A, class1, 15VA current transformers shall be fixed on outgoing side of each transformer feeding panel. 5) Wiring and Terminations Suitable number of din rail 3-pole 2.5sqmm terminals shall be used to terminate the ACB control wires, Current Transformer wiring, and voltage sensing wiring which is to be connected to the Control panel via a multicore control cable. |
01 |
Unit |
Qty |
Item Details |
S/N |
Nos |
01 |
Generator and Transformer feeding Control Panels (8 cubicles) – Synchronizing Panel: 1) The following equipment shall be fixed in each generator control panel DSE8810 Auto Start Load share Control Module Emergency Push Button DC on/off Key Switch Running Mode Selector Switch (Load Share/Fixed Export) Automatic engine battery charger of charging current 5A/24VDC for offline charging. And additional 10A/24VDC charger for online charging with charging ampere meter for each charger. 2) The following items shall be fixed in each Transformer Feeding Panel DSE335 Auto Transfer Switch Control Module Emergency Push Button DC on/off Key Switch 3) A Separate panel shall be fixed with a 22” touch screen monitor and CPU unit to display SCADA data from all DSE units. |
01 |
- Supply of equipment and work carried out under the supply shall cover 1 year warranty.
- The scope of work includes Supply of Generator Synchronizing panel and Transformer Feeding Panel and Testing and Commissioning.
އަންދާސީހިސާބު ހުށަހަޅުއްވާ ފަރާތްތަކުން ހުރިހާ އައިޓަމަކަށް އަގު ހުށަހަޅުއްވަންވާނެއެވެ.
ހުށަހަޅަންވީ ތަކެތި:
- މިތަކެތި ސަޕްލައިކޮށްދެވޭނެ އަގު (ލިސްޓުގައިވާ ހުރިހާ ތަކެއްޗަށް އަގު ހުށަހަޅުއްވަންވާނެއެވެ. އަދި ޖީ.އެސް.ޓީއަށްވާ ޖުމްލަ އަދަދު ވަކިން އެނގޭނެހެން)
- ސަޕްލައިކޮށްދެވޭނެ މުއްދަތު:
- ޓެކްނިކަލް ސްޕެސިފިކޭޝަން:
- ހުށަހަޅާފައިވާ އަންދާސީހިސާބު ބާޠިލުވާ މުއްދަތު މަދުވެގެން 60 ދުވަހަށް ވާންވާނެއެވެ.
- ކުންފުނީގެ މަޢުލޫމާތު (ކުންފުނީގެ ޕްރޮފައިލް، ކުންފުނީގެ ރަޖިސްޓަރީގެ ކޮޕީ، ޖީ.އެސް.ޓީ ސެޓުފިކެޓުގެ ކޮޕީ، މިމަސައްކަތުގައި ކުންފުނީގެ ފަރާތުން މުޢާމަލާތު ކުރާނޭ ފަރާތުގެ ނަން، މަޤާމު އަދި ފޯނު ނަންބަރު)
- ދައުލަތަށް ދައްކަންޖެހޭ ޓެކްސް ކްލިއަރކުރިކަމުގެ ލިޔުން.
- މިފަދަ މަސަައްކަތެއް ކޮށްފައިވާނަމަ މަސައްކަތް ކުރިކަމުގެ ލިޔުން.
އަންދާސީހިސާބުގައި ޕޮއިންޓް ދެވޭގޮތް:
- އަގަށް (ދިވެހި ރުފިޔާ) 60 ޕޮއިންޓް
ހުށަހެޅޭ އެންމެހެޔޮ އަގު / ހުށަހެޅި އަގު 60x
- ބިލަށް ފައިސާ ދެއްކުމަށް ދެވޭ މުއްދަތު (ދުވަސް) 20 ޕޮއިންޓް
ފައިސާ ދެއްކުމަށްދެވޭ މުއްދަތު 20x
- ތަކެތި ފޯރުކޮށްދެވޭނެ މުއްދަތު (ދުވަސް) 20 ޕޮއިންޓް
ހުށަހެޅޭ އެންމެ ކުރު މުއްދަތު / ހުށަހެޅި މުއްދަތު 20x
އަންދާސީހިސާބު ހުށަހަޅުއްވާނީ ތިރީގައި މިދަންނަވާ ގޮތަށް އެޑްރެސް ކޮށްފައެވެ.
މެނޭޖިންގ ޑިރެކްޓަރ ފެނަކަ ކޯޕަރޭޝަން ލިމިޓެޑް އިޢުލާން ނަންބަރު: FNK-K(T)/FNK/IUL/2014/127 ޕޯޓް ކޮމްޕްލެކްސް، 7 ވަނަ ފަންގިފިލާ ހިލާލީމަގު، މާފަންނު މާލެ |
Managing Director Fenaka Corporation Ltd Iulaan No: FNK-K(T)/FNK/IUL/2014/127 Port Complex.7th Floor Hilaalee Magu, Maafannu Male’ |
ބިޑް ހުޅުވުމަށް ހަމަޖެހިފައިވަނީ 22 އޮކްޓޫބަރު 2014 ވާ ބުދަ ދުވަހުގެ 11:00 ގައި ފެނަކަ ކޯޕަރޭޝަން ލިމިޓެޑް (ޕޯޓް ކޮމްޕްލެކްސް، 7 ވަނަ ފަންގިފިލާ) އޮފީހުގެ ޖަލްސާކުރާ މާލަމުގައި މިމަސައްކަތަށް އަންދާސީހިސާބު ހުށަހަޅުއްވަން ވަޑައިގަންނަވާ ފަރާތްތަކުގެ ހާޒިރުގައެވެ. ވީމާ، މި މަސައްކަތް ކޮށްދެއްވުމަށް އެދިވަޑައިގަންނަވާ ފަރާތްތަކުން 22 އޮކްޓޫބަރު 2014 ވާ ބުދަ ދުވަހުގެ 11:00 އަށް އަންދާސީހިސާބު ހުށަހެޅުއްވުން އެދެމެވެ. |
|
ނޯޓް: މަޢުލޫމާތު ފުރިހަމަ ނޫން ބިޑްތައް ބާޠިލު ކުރުމުގެ ފުރިހަމަ އިޚުތިޔާރު ފެނަކަ ކޯޕަރޭޝަނަށް ލިބިގެންވެއެވެ. އަދި ބިޑް ކޮންމެ ވަގުތެއްގައިވެސް ބާޠިލުކުރުމުގެ އިޚުތިޔާރުވެސް ފެނަކަ ކޯޕަރޭޝަން ލިމިޓެޑަށް ލިބިގެންވެއެވެ. މި އިޢުލާނާ ގުޅިގެން އިތުރު މަޢުލޫމާތު ސާފުކުރެއްވުމަށް ގުޅުއްވާނީ ސަރުކާރު ބަންދުނޫން ކޮންމެ ދުވަހަކު ރަސްމީ ގަޑީގައި 3007555 ނަންބަރު ފޯނު މެދުވެރިކޮށް ޕްރޮކިއުމަންޓް ޑިޕާޓްމަންޓަށެވެ. |