Fenaka Corporation Limited
Maldives
400kw Generator Set

ނަންބަރު:FNK-K(T)/FNK/IUL/2017/016

އަންދާސީހިސާބު ބޭނުންވެއްޖެ

މިކުންފުންޏަށް ތިރީގައިވާ މަޢުލޫމާތާއި އެއްގޮތަށް 400 ކިލޯ ވޯޓްގެ 01 (އެކެއް) ޖަނެރޭޓަރ ސެޓް ގަންނަން ބޭނުންވެއެވެ.

#

Description

Unit

Quantity

 

The Standard of the genset shall meet the relevant British Standards.

 

 

1

400 kW prime rated diesel genarator set. 0.8 P.F, 415 Volts, 3 Phase, 4 Wires, 50 Hz at 1500 r.p.m. Powered by Cummins engine origin (UK, USA),And supplier must submit certificate conforming they are Licenced  OEM  cummins manufacturer or assembler.The engine must produce a mechanical power output which should meet the required 400 KW and must be coupled with  400 kW stamford Altenator with pre Installed Droop CT, with remote mounted control panel.The controller should be Deepsea model: 8810 engine controller.
Motorised TP, 800 A, ACB c/w UVT Coil AC 230 V, ("MERLIN GERIN") or equivalent.

Nos.

1

1.1

Engine to be complete with

 

 

 

Heavy electrical flywheel

 

 

 

SAE flywheel housing

 

 

 

Air filters

 

 

 

Lubricating oil filters

 

 

 

Low lubricating oil pressure switch

 

 

 

High engine temperature switch

 

 

 

lub oil sender

 

 

 

water Temperature Sender

 

 

 

Together with all necessary items to run and to protect the engine

 

 

1.1.1

Starting equipment

 

 

 

The engine should be fitted with the following equipment

 

 

 

24 Volt charging altenator (Brushless)

 

 

 

24 Volt starting motor

 

 

 

Fuel Shut-off solenoid

 

 

 

Heavy duty lead acid batteries, supplied in a dry charged condition

 

 

1.1.2

Governing

 

 

 

The engine to be fitted with a close tolerance Cummins Electronic Governing system, which should include efc, actuators, magnetic pickups, etc, including wiring

 

 

1.1.3

Cooling Equipment

 

 

 

Cooling equipment compromising a heavy-duty tropical radiator, together with pusher type cooling fan and guards to be fitted. The radiator core should be elecroplated with silver solder tin plated to prevent early failure due to corrosion. Coupon plated radiators are  acceptable. the radiator has to be mounted on the vibration mounts and it should have enough strength to with stand the radiator.

 

 

1.1.4

Exhaust system

 

 

 

450 mm of stainless steel below type flexible exhaust, together with suitable flanges and fittings shall be supplied for each silencer.

 

 

1.1.5

Alternator

 

 

 

The alternator shall be brushless revolving type altenator, having class H insulation on both the stator and field windings.It shall be built and rated to BS 5000, tropically impregnated with voltage regulation being in the order of +/- 1.5% from no load to full load under the steady state conditions assuming a speed variation not exceeding 4% on the engine.Anti-Condensation Coil to be fitted in the Alternator.

 

 

1.1.6

Generator arrangement and drive

 

 

 

The simplex type base plate is of heavy duty rolled steel constructed, bolted and electrically welded, drilled on the underside to allow the fitting of foundation bolts. The engine and the alternator are to be mounted on a base plate and vibration mounts to be mounted underside of the base plate. The vibration mounts are to be supplied as loose item.

 

 

1.1.7

Fuel system

 

 

 

A fuel day tank of 12 hours capacity complete with level indicator, drain plug, filler, fuel return with fuel outlet connections and a fuel filter fitted with outlet connection is to be mounted.These mounts are are to be suuplied as loose item. All necessary fittings to be supplied in conformity with fuel flow diagram.

Nos.

1

1.2

Factory testing

 

 

 

The generator should be fully tested at the manufacturer workshop in the presence of  client/apointees to check the ratings,overload,functional tests on a dummy load prior to dispatch in case the bidder is unable to provide factory test as mentined, the bidder shall provide an extended warranty of one extre year than mentioned in iteme no 10 of this document.

 

 

1.3

Finishing

 

 

 

After assembling the genset zinc coated self-etching primer should be applied to the complete set.

 

 

1.4

Warranty

 

 

 

Generator set should carry a warranty of one year from the date of commisioning the equipment.

 

 

1.5

Literature and drawings

 

 

1.5.1

How to handle the generation equipment

Nos.

1

1.5.2

Electrical wiring diagram

Nos.

1

1.5.3

Engine operation and maintenance manual

Nos.

1

1.5.4

Engine parts catalogue

Nos.

1

1.5.5

Generator parts catalogue

Nos.

1

1.5.6

Generator operation and maintenance manual

Nos.

1

1.5.7

Generator AVR manual

Nos.

1

1.5.8

Governor control unit manual

Nos.

1

1.5.9

Engine shop manual

Nos.

1

 

*Two separate manuals for the generator set shall be supplied and all the manuals to be enclosed in a fiber box file and the file should be labeled as "FENAKA CORP. LTD.400kW Generator Manuals".

 

 

1.6

Accessories

 

 

 

The Components shall meet the British Standard and ISO standards.  Items are for the above mentioned generator sets.

 

 

1.6.1

Primary silencer barrel(to match engine exhaust)

Nos.

1

1.6.2

Secondary silencer barrel(to match engine exhaust)

Nos.

1

1.6.3

3m Exhaust pipe dia( to match engine exhaust)

Nos.

4

1.6.4

Elbows having dia (to match the engine exhaust)

Nos.

4

1.6.5

Flanges having dia (to match the engine exhaust)

Nos.

8

 

އަންދާސީހިސާބު ހުށަހަޅުއްވާ ފަރާތްތަކުން ހުރިހާ އައިޓަމަކަށް އަގު ހުށަހަޅުއްވަން ވާނެއެވެ.

 

ހުށަހަޅަންވީ ތަކެތި:

  • މިތަކެތި ސަޕްލައިކޮށްދެވޭނެ އަގު. (ލިސްޓްގައިވާ ހުރިހާ ތަކެއްޗަށް އަގު ހުށަހަޅުއްވަންވާނެއެވެ. އަދި ޖީ.އެސް.ޓީއަށްވާ ޖުމްލަ އަދަދު ވަކިން އިނގޭނެހެން.)
  • ސަޕްލައިކޮށްދެވޭނެ މުއްދަތު:
  • ކުންފުނީގެ މަޢުލޫމާތު )ކުންފުނީގެ ޕްރޮފައިލް، ކުންފުނީގެ ރަޖިސްޓަރީގެ ކޮޕީ، ޖީ.އެސް.ޓީ ރަޖިސްޓަރީ ކޮޕީ، ދައުލަތަށް ދައްކަން ޖެހޭ ޓެކްސް ކްލިއަރ ކުރިކަމުގެ ލިޔުން، މިމަސައްކަތުގައި ކުންފުނީގެ ފަރާތުން މުޢާމަލާތު ކުރާނޭ ފަރާތުގެ ނަން، މަޤާމު އަދި ފޯނު ނަންބަރު)
  • މިފަދަ މަސައްކަތެއް ކޮށްފައިވާނަމަ މަސައްކަތް ކުރިކަމުގެ ލިޔުން.
  • ސަޕްލައި ކުރާ ޖަނަރޭޓަރ ސެޓްގެ ޓެކްނިކަލް ސްޕެސިފިކޭޝަން

 

އަންދާސީހިސާބުގައި ޕޮއިންޓްދެވޭ ގޮތް:

  • އަގަށް (ދިވެހި ރުފިޔާ) 40 ޕޮއިންޓް
  • ހުށަހެޅޭ އެންމެހެޔޮ އަގު / ހުށަހެޅި އަގު × 40
  • ސެޓްފިކެޓް އޮފް އޮތެންސިޓީ 05 ޕޮއިންޓް (ޕްރޮޕޯސަލް އާއިއެކު އޮރިޖިނަލް ސެޓްފިކެޓްގެ ކޮފީ ހުށައަޅަންވާނެއެވެ. ނަމަވެސް ސެޓްފިކެޓްގެ އޮރިޖިނަލް އެގްރީމަންޓްގައި ސޮއިކުރައްވަން ވަޑައިގަންނަވާއިރު ގެންނަވަން ވާނެއެވެ.)
  • ޓެކްނިކަލް ކޮމްޕޮނެންޓް 25 ޕޮއިންޓް (ޓެކްނިކަލް އިވަލުއޭޓް ކުރެވޭނީ ކުންފުނީގެ ރިކުއަމެންޓް އާއި އެއްގޮތަށެވެ.)
  • ތަކެތި ފޯރުކޮށްދެވޭނެ މުއްދަތު (ދުވަސް) 30 ޕޮއިންޓް
  • ހުށަހެޅޭ އެންމެ ކުރު މުއްދަތު / ހުށަހެޅި މުއްދަތު × 30

އަންދާސީހިސާބު ހުށަހަޅުއްވާނީ ތިރީގައި މިދަންނަވާ ގޮތަށް އެޑްރެސް ކޮށްފައެވެ.

 

Managing  Director

FenakaCorporationLtd

Iulaan No:FNK-K(T)/FNK/IUL/2017/016

Port Complex.7th Floor

HilaaleeMagu,

Maafannu

Male’

މެނޭޖިންގ ޑިރެކްޓަރ

ފެނަކަ ކޯޕަރޭޝަން ލިމިޓެޑް

އިޢުލާން ނަންބަރ:FNK-K(T)/FNK/IUL/2017/016

ޕޯރޓް ކޮމްޕްލެކްސް، 7ވަނަ ފަންގިފިލާ

ހިލާލީމަގު، މާފަންނު

މާލެ

 

ބިޑް ހުޅުވުމަށް ހަމަޖެހިފައި ވަނީ 2017 މާރޗް 02 ވާ ބުރާސްފަތި ދުވަހުގެ 14:00  ގައި ފެނަކަ ކޯޕަރޭޝަން ލިމިޓެޑް (ޕޯރޓް ކޮމްޕްލެކްސް، 7 ވަނަ ފަންގިފިލާ) އޮފީހުގެ ޖަލްސާ ކުރާ މާލަމުގައި މިމަސައްކަތަށް އަންދާސީހިސާބު ހުށަހަޅުއްވަން ވަޑައިގަންނަވާ ފަރާތްތަކުގެ ހާޟިރުގައެވެ. ވީމާ، މި މަސައްކަތް ކޮށްދެއްވުމަށް އެދިވަޑައިގަންނަވާ ފަރާތްތަކުން 2017 މާރޗް 02 ވާ ބުރާސްފަތި ދުވަހުގެ 14:00  އަށް އަންދާސީހިސާބު ހުށަ ހެޅުއްވުން އެދެމެވެ.

ނޯޓް: މަޢުލޫމާތު ފުރިހަމަ ނޫން ބިޑްތައް ބާޠިލް ކުރުމުގެ ފުރިހަމަ އިޚްތިޔާރު ފެނަކަ ކޯޕަރޭޝަން ލިމިޓެޑަށް ލިބިގެންވެއެވެ. އަދި ބިޑް ކޮންމެ ވަގުތެއްގައި ބާޠިލުކުރުމުގެ އިޙްތިޔާރުވެސް މި ކޯޕަރޭޝަނަށް ލިބިގެންވެއެވެ. މި އިޢުލާނާ ގުޅިގެން އިތުރު މަޢުލޫމާތު ސާފު ކުރެއްވުމަށް ގުޅުއްވާނީ ސަރުކާރު ބަންދުނޫން ކޮންމެ ދުވަހަކު ރަސްމީ ގަޑީގައި 3018260 ނަންބަރު ފޯނު މެދުވެރިކޮށް ޓެންޑަރ އެންޑް ފޮރިން ޕަރޗޭސް ޑިވިޜަނަށެވެ.

 

30 ޖުމާދަލްއޫލާ 1438

27 ފެބުރުވަރީ 2017

 

 

27 February 2017
ހޯދާ